Automatic Transfer System (ATS)

SINGLE PHASE SYSTEMS LIGHT DUTY
Next

Details

These are designed for smart, precision and optimum use of both normal as well as emergency supply to High rise Apartments, Commercial Complexes, Bungalows etc.

Features

  • Wide operating voltage band.
  • Digitally controlled – sanctioned load monitoring very precise.
  • Under Voltage & Over Voltage protection safe guard costly gadgets and fittings.
  • Current monitoring on all sources eliminates over drawing hazards on primary (SEB) and secondary (Emergency) source.
  • Fire retardant Polycarbonate enclosure enhances safety against fire.

Models

MODEL NO
OVERALL DIMENTION (mm)
NORMAL
EMERGENCY
Dp30
108 (H) X 70 (W) X 60 (D)

 

40A
30A
30A
20A
30A
10A
Ep30**
118 (H) x 70 (W) x 60 (D)
30A
15A

**Model Ep30 is specially designed for portable generators only, not recommended for diesel generators, No current limiter inside.

Specification

  • Voltage : 240V AC 50Hz
  • Emergency Current Set Point : Up to 30A factory pre-setted.
  • Voltage Set Point : 160V – 260V optional
  • Normal Current Set Point : Up to 40A optional
  • Response Time : 10 Sec at 25% overload & 4 Sec at 100% overload
  • Resetting Time : 14 Sec
  • Initial Delay : 6 TO 16 Sec after startup
  • Contact Rating : 40A
  • Enclosure : Polycarbonate FR
  • Electrical Endurance : 1X105 operations at rated current
  • Mechanical Endurance : 1X107 operations at rated current