Automatic Transfer System (ATS)

Three Phase Systems Light Duty
Previous Next

Details

In this category wide Varity of ATS are available. These are specially designed for those installation where power sources are Three –Three or One-Three type. In case of three-three configuration load monitoring on phase wise, but in one-three type single phase emergency power distributed over a three phase (TPN) outgoing network. The entire emergency power allotment is available on all three load circuit and may be used for any load on any phase so long the sum total (scalar summation) drawing is within limit, on the other hand the emergency power available only on a pre decided load circuit in one-one type.

Features

  • Precise monitoring of Phase-Neutral Voltage (R-N, Y-N, B-N) provides safe supply to gadgets & fittings.
  • Double screw termination minimizes terminal loose contact.
  • Its Over Load Isolation character enhances operational life.
  • On site up gradation friendly makes it more customized.

Models

MODEL NO
DIMENSIONS (mm)
CAPACITY
NORMAL
Emergency
TYPE

Fp20H

175 (H) X 160 (W) X 145 (D)

25A FP

25A DP

11

25A FP

25A DP

13

25A FP

25A FP

33

Fp25H

175 (H) X 160 (W) X 145 (D)

32A FP

32A DP

11

32A FP

32A DP

13

32A FP

32A FP

33

Fp30H

175 (H) X 160 (W) X 145 (D)

45A FP

45A DP

11

45AFP

45A DP

13

45A FP

45A FP

33

Fp45H

200 (H) X 235 (W) X 145 (D)

63A FP

32A DP

11

63A FP

32A DP

13

63A FP

63A FP

33

Fp50H

200 (H) X 280 (W) X 145 (D)

70A FP

40A DP

13

70A FP

40A FP

33

70A FP

70A FP

33

Specification

  • Voltage : 415V AC 50HZ
  • Resetting Time : 10 Sec
  • Emergency Current Set Point : Up to 70A factory pre-setted
  • Voltage Set Point : 200V – 260V (P-N) optional
  • Normal Current Set Point : Up to 70A optional
  • Response Time : 10 Sec at 25% overload & 4 Sec at 100% overload
  • Initial Delay : 10 Sec after startup
  • Contact Rating : 70A
  • Electrical Endurance : 1X105 operations at rated current
  • Mechanical Endurance : 1X107 operations at rated current